Chapter 2: Loading

Go to the Next Chapter
Go to the Previous Chapter
Go to the Table of Contents for This Manual
Go to the Guides Master Index

Chapter 1 * Chapter 2 * Chapter 3 * Chapter 4 * Chapter 5 * Chapter 6 * Chapter 7 * Chapter 8 * Chapter 9 * Chapter 10 * Chapter 11 * Chapter 12 * Chapter 13 * Chapter 14 * Chapter 15 * Chapter 16 * Chapter 17 * Chapter 18 * Chapter 19


2.1 Loading Overview

The main goal of a finite element analysis is to examine how a structure or component responds to certain loading conditions. Specifying the proper loading conditions is, therefore, a key step in the analysis. You can apply loads on the model in a variety of ways in the ANSYS program. Also, with the help of load step options, you can control how the loads are actually used during solution.

2.2 What Are Loads?

The word loads in ANSYS terminology includes boundary conditions and externally or internally applied forcing functions, as illustrated in Figure 2-1. Examples of loads in different disciplines are:

Structural: displacements, forces, pressures, temperatures (for thermal strain), gravity

Thermal: temperatures, heat flow rates, convections, internal heat generation, infinite surface

Magnetic: magnetic potentials, magnetic flux, magnetic current segments, source current density, infinite surface

Electric: electric potentials (voltage), electric current, electric charges, charge densities, infinite surface

Fluid: velocities, pressures

Figure 2-1 "Loads" include boundary conditions as well as other types of loading

Loads are divided into six categories: DOF constraints, forces (concentrated loads), surface loads, body loads, inertia loads, and coupled-field loads.

Definitions of other loads-related terms appear below.

2.3 Load Steps, Substeps, and Equilibrium Iterations

A load step is simply a configuration of loads for which a solution is obtained. In a linear static or steady-state analysis, you can use different load steps to apply different sets of loads-wind load in the first load step, gravity load in the second load step, both loads and a different support condition in the third load step, and so on. In a transient analysis, multiple load steps apply different segments of the load history curve.

The ANSYS program uses the set of elements which you select for the first load step for all subsequent load steps, no matter which element sets you specify for the later steps. To select an element set, you use either of the following:

Command(s):

GUI:

Utility Menu>Select>Entities

Figure 2-2 shows a load history curve that requires three load steps-the first load step for the ramped load, the second load step for the constant portion of the load, and the third load step for load removal.

Figure 2-2 Using multiple load steps to specify a transient load history curve

Substeps are points within a load step at which solutions are calculated. You use them for different reasons:

Equilibrium iterations are additional solutions calculated at a given substep for convergence purposes. They are iterative corrections used only in nonlinear analyses (static or transient), where convergence plays an important role.

Consider, for example, a two-dimensional, nonlinear static magnetic analysis. To obtain an accurate solution, two load steps are commonly used. (Figure 2-3 illustrates this.)

Figure 2-3 Load steps, substeps, and equilibrium iterations

2.4 The Role of Time in Tracking

The ANSYS program uses time as a tracking parameter in all static and transient analyses, whether they are or are not truly time-dependent. The advantage of this is that you can use one consistent "counter" or "tracker" in all cases, eliminating the need for analysis-dependent terminology. Moreover, time always increases monotonically, and most things in nature happen over a period of time, however brief the period may be.

Obviously, in a transient analysis or in a rate-dependent static analysis (creep or viscoplasticity), time represents actual, chronological time in seconds, minutes, or hours. You assign the time at the end of each load step (using the TIME command) while specifying the load history curve. To assign time, use one of the following:

Command(s):

GUI:

Main Menu>Preprocessor>Loads>Time/Frequenc>Time and Substps Main Menu>Preprocessor>Loads>Time/Frequenc>Time - Time Step
Main Menu>Solution>Time/Frequenc>Time and Substps
Main Menu>Solution>Time/Frequenc>Time - Time Step

In a rate-independent analysis, however, time simply becomes a counter that identifies load steps and substeps. By default, the program automatically assigns time=1.0 at the end of load step 1, time=2.0 at the end of load step 2, and so on. Any substeps within a load step will be assigned the appropriate, linearly interpolated time value. By assigning your own time values in such analyses, you can establish your own tracking parameter. For example, if a load of 100 units is to be applied incrementally over one load step, you can specify time at the end of that load step to be 100, so that the load and time values are synchronous.

In the postprocessor, then, if you obtain a graph of deflection versus time, it means the same as deflection versus load. This technique is useful, for instance, in a large-deflection buckling analysis where the objective may be to track the deflection of the structure as it is incrementally loaded.

Time takes on yet another meaning when you use the arc-length method in your solution. In this case, time equals the value of time at the beginning of a load step, plus the value of the arc-length load factor (the multiplier on the currently applied loads). ALLF does not have to be monotonically increasing (that is, it can increase, decrease, or even become negative), and it is reset to zero at the beginning of each load step. As a result, time is not considered a "counter" in arc-length solutions.

The arc-length method is an advanced solution technique. For more information about using it, see Chapter 8 of the ANSYS Structural Analysis Guide.

A load step is a set of loads applied over a given time span. Substeps are time points within a load step at which intermediate solutions are calculated. The difference in time between two successive substeps can be called a time step or time increment. Equilibrium iterations are iterative solutions calculated at a given time point purely for convergence purposes.

2.5 Stepped Versus Ramped Loads

When you specify more than one substep in a load step, the question of whether the loads should be stepped or ramped arises.

Figure 2-4 Stepped versus ramped loads

The KBC command (Main Menu>Solution>Time/Frequenc>Freq & Substeps, Main Menu>Solution>Time/Frequenc>Time and Substps, or Main Menu>Solution>Time/Frequenc>Time & Time Step) is used to indicate whether loads are ramped or stepped. KBC,0 indicates ramped loads, and KBC,1 indicates stepped loads. The default depends on the discipline and type of analysis and if SOLCONTROL is ON or OFF.

Load step options is a collective name given to options that control load application, such as time, number of substeps, the time step, and stepping or ramping of loads. Other types of load step options include convergence tolerances (used in nonlinear analyses), damping specifications in a structural analysis, and output controls.

2.6 How to Apply Loads

You can apply most loads either on the solid model (on keypoints, lines, and areas) or on the finite element model (on nodes and elements). For example, you can specify forces at a keypoint or a node. Similarly, you can specify convections (and other surface loads) on lines and areas or on nodes and element faces. No matter how you specify the loads, the solver expects all loads to be in terms of the finite element model. Therefore, if you specify loads on the solid model, the program automatically transfers them to the nodes and elements at the beginning of solution.

2.6.1 Solid-Model Loads: Advantages and Disadvantages

Advantages

Disadvantages

Notes About Solid-Model Loads

As mentioned earlier, solid-model loads are automatically transferred to the finite element model at the beginning of solution. The ANSYS program overwrites any loads that already exist on corresponding finite element entities.

Deleting solid-model loads also deletes all corresponding finite-element loads.

2.6.2 Finite-Element Loads: Advantages and Disadvantages

Advantages

Disadvantages

The next few subsections discuss how to apply each category of loads-constraints, forces, surface loads, body loads, inertia loads, and coupled-field loads-and then explain how to specify load step options.

2.6.3 DOF Constraints

Table 2-1 shows the degrees of freedom that can be constrained in each discipline and the corresponding ANSYS labels. Any directions implied by the labels (such as UX, ROTZ, AY, etc.) are in the nodal coordinate system. For a description of different coordinate systems, see the ANSYS Modeling and Meshing Guide.

Table 2-2 shows the commands to apply, list, and delete DOF constraints. Notice that you can apply constraints on nodes, keypoints, lines, and areas.

Table 2-1 DOF constraints available in each discipline

Discipline

Degree of Freedom

ANSYS Label

Structural

Translations
Rotations

UX, UY, UZ
ROTX, ROTY, ROTZ

Thermal

Temperature

TEMP

Magnetic

Vector Potentials
Scalar Potential

AX, AY, AZ
MAG

Electric

Voltage

VOLT

Fluid

Velocities
Pressure
Turbulent Kinetic Energy
Turbulent Dissipation Rate

VX, VY, VZ
PRES
ENKE
ENDS

Table 2-2 Commands for DOF constraints

Location

Basic Commands

Additional Commands

Nodes

D, DLIST, DDELE

DSYM, DSCALE, DCUM

Keypoints

DK, DKLIST, DKDELE

-

Lines

DL, DLLIST, DLDELE

-

Areas

DA, DALIST, DADELE

-

Transfer

SBCTRAN

DTRAN

Below are examples of some of the GUI paths you can use to apply DOF constraints:

GUI:

Main Menu>Preprocessor>-Loads->Apply>load type>On Nodes
Utility Menu>List>Loads>DOF Constraints>On Keypoints
Main Menu>Solution>Apply>load type>On Lines

See the ANSYS Commands Reference for additional GUI path information and for descriptions of the commands listed in Table 2-2.

2.6.4 Applying Symmetry or Antisymmetry Boundary Conditions

Use the DSYM command to apply symmetry or antisymmetry boundary conditions on a plane of nodes. The command generates the appropriate DOF constraints. See the ANSYS Commands Reference for the list of constraints generated.

In a structural analysis, for example, a symmetry boundary condition means that out-of-plane translations and in-plane rotations are set to zero, and an antisymmetry condition means that in-plane translations and out-of-plane rotations are set to zero. (See Figure 2-5.) All nodes on the symmetry plane are rotated into the coordinate system specified by the KCN field on the DSYM command. The use of symmetry and antisymmetry boundary conditions is illustrated in Figure 2-6. The DL and DA commands work in a similar fashion when you apply symmetry or antisymmetry conditions on lines and areas.

You can use the DL and DA commands to apply velocities, pressures, temperatures, and turbulence quantities on lines and areas for FLOTRAN analyses. At your discretion, you can apply boundary conditions at the endpoints of the lines and the edges of areas.

Note-If the node rotation angles that are in the database while you are using the general postprocessor (POST1) are different from those used in the solution being postprocessed, POST1 may display incorrect results. This condition usually results if you introduce node rotations in a second or later load step by applying symmetry or antisymmetry boundary conditions. Erroneous cases display the following message in POST1 when you execute the SET command (Utility Menu> List>Results>Load Step Summary):

Warning: Cumulative iteration 1 may have been solved using different model or boundary condition data than is currently stored. POST1 results may be erroneous unless you resume from a .db file matching this solution.

Figure 2-5 Symmetry and antisymmetry boundary conditions in a structural analysis

Figure 2-6 Examples of using symmetry and antisymmetry boundary conditions

2.6.5 Transferring Constraints

To transfer constraints that have been applied to the solid model to the corresponding finite element model, use one of the following:

Command(s):

GUI:

Main Menu>Preprocessor>Loads>Operate>-Transfer to FE->Constraints
Main Menu>Solution>Operate>-Transfer to FE->Constraints

To transfer all solid model boundary conditions, use one of the following:

Command(s):

GUI:

Main Menu>Preprocessor>Loads>Operate>-Transfer to FE->
All Solid Lds
Main Menu>Solution>Operate>-Transfer to FE->All Solid Lds

2.6.5.1 Resetting Constraints

By default, if you repeat a DOF constraint on the same degree of freedom, the new specification replaces the previous one. You can change this default to add (for accumulation) or ignore with the DCUM command (Main Menu> Preprocessor>Loads>Settings>-Replace vs. Add->Constraints). For example:

NSEL,...          	! Selects a set of nodes
D,ALL,VX,40	! Sets VX = 40 at all selected nodes
D,ALL,VX,50	! Changes VX value to 50 (replacement)
DCUM,ADD          	! Subsequent D's to be added
D,ALL,VX,25	! VX = 50+25 = 75 at all selected nodes
DCUM,IGNORE       	! Subsequent D's to be ignored
D,ALL,VX,1325     	! These VX values are ignored!
DCUM              	! Resets DCUM to default (replacement)
See the ANSYS Commands Reference for discussions of the NSEL, D, and DCUM commands.

Any DOF constraints you set with DCUM stay set until another DCUM is issued. To reset the default setting (replacement), simply issue DCUM without any arguments.

2.6.5.2 Scaling Constraint Values

You can scale existing DOF constraint values as follows:

Command(s):

GUI:

Main Menu>Preprocessor>Loads>Operate>-Scale FE Loads->Constraints
Main Menu>Solution>Operate>-Scale FE Loads->Constraints

Both the DSCALE and DCUM commands work on all selected nodes and also on all selected DOF labels. By default, DOF labels that are active are those associated with the element types in the model:

Command(s):

GUI:

Main Menu>Preprocessor>Loads>Operate>-Scale FE Loads->Constraints (or Forces)
Main Menu>Preprocessor>Loads>Settings>-Replace vs. Add->Constraints
(or Forces)
Main Menu>Solution>Operate>-Scale FE Loads->Constraints
(or Forces)
Main Menu>Solution>Settings>-Replace vs. Add->Constraints
(or Forces)

For example, if you want to scale only VX values and not any other DOF label, you can use the following commands:

DOFSEL,S,VX       	! Selects VX label
DSCALE,0.5	! Scales VX at all selected nodes by 0.5
DOFSEL,ALL        	! Reactivates all DOF labels
When scaling temperature constraints (TEMP) in a thermal analysis, you can use the TBASE field on the DSCALE command to scale the temperature offset from a base temperature (that is, to scale |TEMP-TBASE|) rather than the actual temperature values. The following figure illustrates this.

Figure 2-7 Scaling temperature constraints with DSCALE



2.6.5.3 Resolution of Conflicting Constraint Specifications

You need to be aware of the possibility of conflicting DK, DL, and DA constraint specifications and how the ANSYS program handles them. The following conflicts can arise:

The ANSYS program transfers constraints that have been applied to the solid model to the corresponding finite element model in the following sequence:

1. In ascending area number order, DOF DA constraints transfer to nodes on areas (and bounding lines and keypoints).

2. In ascending area number order, SYMM and ASYM DA constraints transfer to nodes on areas (and bounding lines and keypoints).

3. In ascending line number order, DOF DL constraints transfer to nodes on lines (and bounding keypoints).

4. In ascending line number order, SYMM and ASYM DL constraints transfer to nodes on lines (and bounding keypoints).

5. DK constraints transfer to nodes on keypoints (and on attached lines, areas, and volumes if expansion conditions are met).

Accordingly, for conflicting constraints, DK commands overwrite DL commands and DL commands overwrite DA commands. For conflicting constraints, constraints specified for a higher line number or area number overwrite the constraints specified for a lower line number or area number, respectively. The constraint specification issue order does not matter.

Note-Any conflict detected during solid model constraint transfer produces a warning similar to the following:

Changing the value of DK, DL, or DA constraints between solutions may produce many of these warnings at the 2nd or later solid BC transfer. These can be prevented if you delete the nodal D constraints between solutions using DADEL, DLDEL, and/or DDELE.

Note-For conflicting constraints on flow degrees of freedom VX, VY, or VZ, zero values (wall conditions) are always given priority over non-zero values (inlet/outlet conditions). "Conflict" in this situation will not produce a warning.

2.6.6 Forces (Concentrated Loads)

Table 2-3 shows a list of forces available in each discipline and the corresponding ANSYS labels. Any directions implied by the labels (such as FX, MZ, CSGY, etc.) are in the nodal coordinate system. (See Chapter 3 of the ANSYS Modeling and Meshing Guide for a description of different coordinate systems.) Table 2-4 lists the commands to apply, list, and delete forces. Notice that you can apply them at nodes as well as keypoints.

Table 2-3 "Forces" available in each discipline

Discipline

Force

ANSYS Label

Structural

Forces
Moments

FX, FY, FZ
MX, MY, MZ

Thermal

Heat Flow Rate

HEAT

Magnetic

Current Segments
Magnetic Flux
Electrical Charge

CSGX, CSGY, CSGZ
FLUX
CHRG

Electric

Current
Charge

AMPS
CHRG

Fluid

Fluid Flow Rate

FLOW

Table 2-4 Commands for applying force loads

Location

Basic Commands

Additional Commands

Nodes

F, FLIST, FDELE

FSCALE, FCUM

Keypoints

FK, FKLIST, FKDELE

-

Transfer

SBCTRAN

FTRAN

Below are examples of some of the GUI paths to use for applying force loads:

GUI:

Main Menu>Preprocessor>-Loads->Apply>load type>On Nodes
Utility Menu>List>Loads>Forces>On Keypoints
Main Menu>Solution>-Loads->Apply>load type>On Lines

See the ANSYS Commands Reference for descriptions of the commands listed in Table 2-4.

2.6.6.1 Repeating a Force

By default, if you repeat a force at the same degree of freedom, the new specification replaces the previous one. You can change this default to add (for accumulation) or ignore by using one of the following:

Command(s):

GUI:

Main Menu>Preprocessor>-Loads->Settings>Forces
Main Menu>Solution>-Loads->Settings>-Replace vs. Add->Forces

For example:

F,447,FY,3000	! Applies FY = 3000 at node 447
F,447,FY,2500     	! Changes FY value to 2500 (replacement)
FCUM,ADD          	! Subsequent F's to be added
F,447,FY,-1000	! FY = 2500-1000 = 1500 at node 447
FCUM,IGNORE       	! Subsequent F's to be ignored
F,25,FZ,350       	! This force is ignored!
FCUM              	! Resets FCUM to default (replacement)
See the ANSYS Commands Reference for a discussion of the F and FCUM commands.

Any force set via FCUM stays set until another FCUM is issued. To reset the default setting (replacement), simply issue FCUM without any arguments.

2.6.6.2 Scaling Force Values

The FSCALE command allows you to scale existing force values:

Command(s):

GUI:

Main Menu>Preprocessor>Loads>Operate>-Scale FE Loads->Forces
Main Menu>Solution>Operate>-Scale FE Loads->Forces

FSCALE and FCUM work on all selected nodes and also on all selected force labels. By default, force labels that are active are those associated with the element types in the model. You can select a subset of these with the DOFSEL command. For example, to scale only FX values and not any other label, you can use the following commands:

DOFSEL,S,FX       	! Selects FX label
FSCALE,0.5	! Scales FX at all selected nodes by 0.5
DOFSEL,ALL        	! Reactivates all DOF labels

2.6.6.3 Transferring Forces

To transfer forces that have been applied to the solid model to the corresponding finite element model, use one of the following:

Command(s):

GUI:

Main Menu>Preprocessor>Loads>Operate>-Transfer to FE->Forces
Main Menu>Solution>Operate>-Transfer to FE->Forces

To transfer all solid model boundary conditions, use the SBCTRAN command:

GUI:

Main Menu>Preprocessor>Loads>Operate>-Transfer to FE->All Solid Lds
Main Menu>Solution>Operate>-Transfer to FE->All Solid Lds

2.6.7 Surface Loads

Table 2-5 shows surface loads available in each discipline and their corresponding ANSYS labels. The commands to apply, list, and delete surface loads are shown in Table 2-6. You can apply them at nodes and elements, as well as at lines and areas.

Table 2-5 Surface loads available in each discipline

Discipline

Surface Load

ANSYS Label

Structural

Pressure

PRES 1.

Thermal

Convection
Heat Flux
Infinite Surface

CONV
HFLUX
INF

Magnetic

Maxwell Surface
Infinite Surface

MXWF
INF

Electric

Maxwell Surface
Surface Charge Density
Infinite Surface

MXWF
CHRGS
INF

Fluid

Fluid-Structure Interface
Impedance

FSI
IMPD

All

Superelement Load Vector

SELV

1. Do not confuse this with the PRES degree of freedom

Table 2-6 Commands for applying surface loads

Location

Basic Commands

Additional Commands

Nodes

SF, SFLIST, SFDELE

SFSCALE,SFCUM,SFFUN,
SFGRAD

Elements

SFE, SFELIST, SFEDELE

SFBEAM,SFFUN,SFGRAD

Lines

SFL, SFLLIST, SFLDELE

SFGRAD

Areas

SFA, SFALIST, SFADELE

SFGRAD

Transfer

SFTRAN

-

Below are examples of some of the GUI paths to use for applying surface loads.

GUI:

Main Menu>Preprocessor>-Loads->Apply>load type>On Nodes
Utility Menu>List>Loads>Surface Loads>On Elements
Main Menu>Solution>-Loads->Apply>load type>On Lines

See the descriptions of the commands listed in Table 2-6 in the ANSYS Commands Reference for more information.

Note-The ANSYS program stores surface loads specified on nodes internally in terms of elements and element faces. Therefore, if you use both nodal and element surface load commands for the same surface, only the last specification will be used.

ANSYS applies pressures on axisymmetric shell elements or beam elements on their inner or outer surfaces, as appropriate. In-plane pressure load vectors for layered shells (SHELL91 and SHELL99) are applied on the nodal plane. KEYOPT(11) determines the location of the nodal plane within the shell. When you use flat elements to represent doubly curved surfaces, values which should be a function of the active radius of the meridian will be inaccurate.

2.6.7.1 Applying Pressure Loads on Beams

To apply pressure loads on the lateral faces and the two ends of beam elements, use one of the following:

Command(s):

GUI:

Main Menu>Preprocessor>Loads>Apply>-Structural->Pressure>On Beams
Main Menu>Solution>Apply>-Structural->Pressure>On Beams

You can apply lateral pressures, which have units of force per unit length, both in the normal and tangential directions. The pressures may vary linearly along the element length, and can be specified on a portion of the element, as shown in the following figure. You can also reduce the pressure down to a force (point load) at any location on a beam element by setting the JOFFST field to -1. End pressures have units of force.

Figure 2-8 Example of beam surface loads

2.6.7.2 Specifying Node Number Versus Surface Load

The SFFUN command (Main Menu>Preprocessor>Loads>Settings>-For Surface Ld->Node Function, or Main Menu>Solution>Settings>-For Surface Ld->Node Function) specifies a "function" of node number versus surface load to be used when you apply surface loads on nodes or elements. It is useful when you want to apply nodal surface loads calculated elsewhere (by another software package, for instance). You should first define the function in the form of an array parameter containing the load values. The location of the value in the array parameter implies the node number. For example, the array parameter shown below specifies four surface load values at nodes 1, 2, 3, and 4, respectively.

Assuming that these are heat flux values, you would apply them as follows:

*DIM,ABC,ARRAY,4              ! Declares dimensions of array parameter ABC
ABC(1)=400,587.2,965.6,740    ! Defines values for ABC
SFFUN,HFLUX,ABC(1)            ! ABC to be used as heat flux function
SF,ALL,HFLUX,100              ! Heat flux of 100 on all selected nodes,
                              !  100 + ABC(i) at node i.
See the ANSYS Commands Reference for a discussion of the *DIM, SFFUN, and SF commands.

The SF command in the example above specifies a heat flux of 100 on all selected nodes. If nodes 1 through 4 are part of the selected set, those nodes are assigned heat fluxes of 100+ABC(i): 100+400=500 at node 1, 100+587.2=687.2 at node 2, and so on.

Note-What you specify with the SFFUN command stays active for all subsequent SF and SFE commands. To remove the specification, simply use SFFUN without any arguments.

2.6.7.3 Specifying a Gradient Slope

You can use either of the following to specify that a gradient (slope) is to be used for subsequently applied surface loads:

Command(s):

GUI:

Main Menu>Preprocessor>Loads>Settings>-For Surface Ld->Gradient
Main Menu>Solution>Settings>-For Surface Ld->Gradient

You can also use this command to apply a linearly varying surface load, such as hydrostatic pressure on a structure immersed in water.

To create the gradient specification, you specify the type of load to be controlled (the Lab argument), the coordinate system and coordinate direction the slope is defined in (SLKCN and Sldir, respectively), the coordinate location where the value of the load (as specified on a subsequent surface load command) will be in effect (SLZER), and the slope (SLOPE).

For example, the hydrostatic pressure (Lab=PRES) shown in Figure 2-9 is to be applied. Its slope can be specified in the global Cartesian system (SLKCN=0) in the Y direction (Sldir=Y). The pressure (to be specified as 500 on a subsequent SF command) is to have its as-specified value (500) at Y=0 (SLZER=0), and will decrease by 25 units per length in the positive Y direction (SLOPE=-25).

Figure 2-9 Example of surface load gradient [SFGRAD]

The commands would be as follows:

SFGRAD,PRES,0,Y,0,-25 	! Y slope of -25 in global Cartesian
NSEL,...               	! Select nodes for pressure application
SF,ALL,PRES,500         	! Pressure at all selected nodes:
                        	!  500 at Y=0, 250 at Y=10, 0 at Y=20
When specifying the gradient in a cylindrical coordinate system (SLKCN=1, for example), keep some additional points in mind. First, SLZER is in degrees, and SLOPE is in units of load/degree. Second, you need to follow two guidelines:

Guideline 1: Set CSCIR (for controlling the coordinate system singularity location) such that the surface to be loaded does not cross the coordinate system singularity.

Guideline 2: Choose SLZER to be consistent with the CSCIR setting. That is, SLZER should be between ±180° if the singularity is at 180° [CSCIR,KCN,0], and SLZER should be between 0° and 360° if the singularity is at 0° [CSCIR,KCN,1].

The following example illustrates why these guidelines are suggested. Consider a semi-circular shell as shown in Figure 2-10, located in a local cylindrical system 11. The shell is to be loaded with an external tapered pressure, tapering from 400 at -90° to 580 at +90°. By default, the singularity in the cylindrical system is located at 180°, therefore the coordinates of the shell range from -90° to +90°. The following commands will apply the desired pressure load:

SFGRAD,PRES,11,Y,-90,1 	! Slope the pressure in the theta direction
                          	!   of C.S. 11.  Specified pressure in effect
                           	!   at -90 degrees, tapering at 1 unit per degree
SF,ALL,PRES,400         	! Pressure at all selected nodes:
                        	!  400 at -90 deg., 490 at 0 deg., 580 at +90 deg.
At -90°, the pressure value is 400 (as specified), increasing as increases by a slope of 1 unit per degree, to 490 at 0° and 580 at +90°.

Figure 2-10 Tapered load on a cylindrical shell

You might be tempted to use 270°, instead of -90°, for SLZER:

SFGRAD,PRES,11,Y,270,1 	! Slope the pressure in the theta direction
                          	!   of C.S. 11.  Specified pressure in effect
                           	!   at 270 degrees, tapering at 1 unit per degree
SF,ALL,PRES,400         	! Pressure at all selected nodes:
                        	!  400 at -90 deg., 490 at 0 deg., 580 at +90 deg.
However, as shown on the left in Figure 2-11, this will result in a tapered load much different than intended. This is because the singularity is still located at 180° (the coordinates still range from -90° to +90°), but SLZER is not between -180° and +180°. As a result, the program will use a load value of 400 at 270°, and a slope of 1 unit per degree to calculate the applied load values of 220 at +90°, 130 at 0°, and 40 at -90°. You can avoid this behavior by following the second guideline, that is, choosing SLZER to be between ±180° when the singularity is at 180°, and between 0° and 360° when the singularity is at 0°.

Figure 2-11 Violation of guideline 2 (left) and guideline 1 (right)

Suppose that you change the singularity location to 0°, thereby satisfying the second guideline (270° is then between 0° and 360°). But then the coordinates of the nodes range from 0° to +90° for the upper half of the shell, and 270° to 360° for the lower half. The surface to be loaded crosses the singularity, a violation of Guideline 1:

CSCIR,11,1              	! Change singularity to 0 degrees
SFGRAD,PRES,11,Y,270,1 	! Slope the pressure in the theta direction
                          	!   of C.S. 11.  Specified pressure in effect
                           	!   at 270 degrees, tapering at 1 unit per degree
SF,ALL,PRES,400         	! Pressure at all selected nodes:
                        	!  400 at 270 deg., 490 at 360 deg., 220 at +90 deg.
                            	!  and 130 at 0 deg.
Again the program will use a load value of 400 at 270° and a slope of 1 unit per degree to calculate the applied load values of 400 at 270°, 490 at 360°, 220 at 90°, and 130 at 0°. Violating Guideline 1 will cause a singularity in the tapered load itself, as shown on the right in Figure 2-11. Due to node discretization, the actual load applied will not change as abruptly at the singularity as it is shown in the figure. Instead, the node at 0° will have the load value of, in the case shown, 130, while the next node clockwise (say, at 358°) will have a value of 488.

Note-The SFGRAD specification stays active for all subsequent load application commands. To remove the specification, simply issue SFGRAD without any arguments. Also, if an SFGRAD specification is active when a load step file is read, the program erases the specification before reading the file.

Large deflection effects can change the node locations significantly. The SFGRAD slope and load value calculations, which are based on node locations, are not updated to account for these changes. If you need this capability, use SURF19 or SURF153 with face 3 loading or SURF22 or SURF154 with face 4 loading.

2.6.7.4 Repeating a Surface Load

By default, if you repeat a surface load at the same surface, the new specification replaces the previous one. You can change this default to add (for accumulation) or ignore using one of the following:

Command(s):

GUI:

Main Menu>Preprocessor>Loads>Settings>-Replace vs. Add->Surface Loads
Main Menu>Solution>Settings>-Replace vs. Add->Surface Loads

Any surface load you set stays set until you issue another SFCUM command. To reset the default setting (replacement), simply issue SFCUM without any arguments. The SFSCALE command allows you to scale existing surface load values. Both SFCUM and SFSCALE act only on the selected set of elements. The Lab field allows you to choose the surface load label.

2.6.7.5 Transferring Surface Loads

To transfer surface loads that have been applied to the solid model to the corresponding finite element model, use one of the following:

Command(s):

GUI:

Main Menu>Preprocessor>Loads>Operate>-Transfer to FE->Surface Loads
Main Menu>Solution>Operate>-Transfer to FE->Surface Loads

To transfer all solid model boundary conditions, use the SBCTRAN command. (See Section 2.6.3 for a description of DOF constraints.)

2.6.7.6 Using Surface Effect Elements to Apply Loads

Sometimes, you may need to apply a surface load that the element type you are using does not accept. For example, you may need to apply uniform tangential (or any non-normal or directed) pressures on structural solid elements, radiation specifications on thermal solid elements, etc. In such cases, you can overlay the surface where you want to apply the load with surface effect elements and use them as a "conduit" to apply the desired loads. Currently, the following surface effect elements are available: SURF19, SURF151, and SURF153 for 2-D models and SURF22, SURF152, and SURF154 for 3-D models.

2.6.8 Body Loads

Table 2-7 shows all body loads available in each discipline and their corresponding ANSYS labels. The commands to apply, list, and delete body loads are shown in Table 2-8. You can apply them at nodes, elements, keypoints, lines, areas, and volumes.

Table 2-7 Body loads available in each discipline

Discipline

Body Load

ANSYS Label

Structural

Temperature

Fluence

TEMP 1.

FLUE

Thermal

Heat Generation Rate

HGEN

Magnetic

Temperature

Current Density

Virtual Displacement

Voltage Drop

TEMP 1.

JS

MVDI

VLTG

Electric

Temperature

Volume Charge Density

TEMP 1.

CHRGD

Fluid

Heat Generation Rate

Force Density

HGEN

FORC

1. Do not confuse this with the TEMP degree of freedom.

Table 2-8 Commands for applying body loads

Location

Basic Commands

Additional Commands

Nodes

BF, BFLIST, BFDELE

BFSCALE, BFCUM, BFUNIF

Elements

BFE, BFELIST, BFEDELE

BFESCAL, BFECUM

Keypoints

BFK, BFKLIST, BFKDELE

-

Lines

BFL, BFLLIST, BFLDELE

-

Areas

BFA, BFALIST, BFADELE

-

Volumes

BFV, BFVLIST, BFVDELE

-

Transfer

BFTRAN

-

For the particular body loads that you can apply, list or delete with any of the commands listed in Table 2-8, see the ANSYS Commands Reference.

Below are examples of some of the GUI paths to use for applying body loads:

GUI:

Main Menu>Preprocessor>Loads>-Loads-Apply>load type>On Nodes
Utility Menu>List>Loads>Body Loads>On Picked Elems
Main Menu>Solution>-Loads-Apply>load type>On Keypoints
Utility Menu>List>Loads>Body Loads>On Picked Lines
Main Menu>Solution>-Loads-Apply>load type>On Volumes

See the ANSYS Commands Reference for descriptions of the commands listed in Table 2-8.

Note-Body loads you specify on nodes are independent of those specified on elements. For a given element, ANSYS determines which loads to use as follows:

2.6.8.1 Specifying Body Loads for Elements

The BFE command specifies body loads on an element-by-element basis. However, you can specify body loads at several locations on an element, requiring multiple load values for one element. The locations used vary from element type to element type, as shown in the examples that follow. The defaults (for locations where no body loads are specified) also vary from element type to element type. Therefore, be sure to refer to the element documentation online or in the ANSYS Elements Reference before you specify body loads on elements.

Figure 2-12 BFE load locations for 2-D and 3-D solids

Figure 2-13 BFE load locations for shell elements (SHELL63 on the left, SHELL51 on the right)

Figure 2-14 BFE load locations for beam and pipe elements

2.6.8.2 Specifying Body Loads for Keypoints

You can use the BFK command to apply body loads at keypoints. If you specify loads at the corner keypoints of an area or a volume, all load values must be equal for the loads to be transferred to the interior nodes of the area or volume. If you specify unequal load values, they will be transferred (with linear interpolation) to only the nodes along the lines that connect the keypoints. Figure 2-15 illustrates this:

Figure 2-15 Transfers of BFK loads to nodes

2.6.8.3 Specifying Body Loads on Lines, Areas and Volumes

You can use the BFL, BFA , and BFV commands to specify body loads on lines, areas, and volumes of a solid model, respectively. Body loads on lines of a solid model are transferred to the corresponding nodes of the finite element model. Body loads on areas or volumes of a solid model are transferred to the corresponding elements of the finite element model.

2.6.8.4 Specifying a Uniform Body Load

The BFUNIF command specifies a uniform body load at all nodes in the model. Most often, you use this command or path to specify a uniform temperature field; that is, a uniform temperature body load in a structural analysis or a uniform starting temperature in a transient or nonlinear thermal analysis. This is also the default temperature at which the ANSYS program evaluates temperature-dependent material properties.

Another way to specify a uniform temperature is as follows:

Command(s):

GUI:

Main Menu>Preprocessor>Loads>Apply>Temperature>Uniform Temp
Main Menu>Preprocessor>Loads>Settings>Uniform Temp
Main Menu>Solution>Apply>Temperature>Uniform Temp
Main Menu>Solution>Settings>Uniform Temp

2.6.8.5 Repeating a Body Load Specification

By default, if you repeat a body load at the same node or same element, the new specification replaces the previous one. You can change this default to ignore using one of the following:

Command(s):

GUI:

Main Menu>Preprocessor>Loads>Settings>Nodal Body Ld
Main Menu>Preprocessor>Loads>Settings>Elem Body Lds
Main Menu>Solution>Settings>Nodal Body Ld
Main Menu>Solution>Settings>Elem Body Lds

The settings you specify with either command or its equivalent GUI paths stay set until they are reuse the command or path. To reset the default setting (replacement), simply issue the commands or choose the paths without any arguments.

2.6.8.6 Transferring Body Loads

To transfer body loads that have been applied to the solid model to the corresponding finite element model, use one of the following:

Command(s):

GUI:

Main Menu>Preprocessor>Loads>Operate>Body Loads
Main Menu>Solution>Operate>Body Loads

To transfer all solid model boundary conditions, use the SBCTRAN command. (See Section 2.6.3 for a description of DOF constraints.)

2.6.8.7 Scaling Body Load Values

You can scale existing body load values using these commands:

Command(s):

GUI:

Main Menu>Preprocessor>Loads>Operate>Nodal Body Ld
Main Menu>Solution>Operate>Nodal Body Ld

Command(s):

GUI:

Main Menu>Preprocessor>Loads>Operate>Elem Body Lds
Main Menu>Solution>Operate>Elem Body Lds

BFCUM and BFSCALE act on the selected set of nodes, whereas BFECUM and BFESCAL act on the selected set of elements.

2.6.8.8 Resolution of Conflicting Body Load Specifications

You need to be aware of the possibility of conflicting BFK, BFL, BFA, and BFV body load specifications and how the ANSYS program handles them.

BFV, BFA, and BFL specifications transfer to associated volume, area, and line elements, respectively, where they exist. Where elements do not exist, they transfer to the nodes on the volumes, areas, and lines, including nodes on the region boundaries. The possibility of conflicting specifications depends upon how BFV, BFA, BFL and BFK are used as described by the following cases.

CASE A: There are elements for every BFV, BFA, or BFL, and every element belongs to a volume, area or line having a BFV, BFA, or BFL, respectively.

CASE B: There are elements for every BFV, BFA, or BFL, but some elements do not belong to a volume area or line having a BFV, BFA, or BFL.

CASE C: At least one BFV, BFA, or BFL cannot transfer to elements.

In "Case C" situations, the following conflicts can arise:

The ANSYS program transfers body loads that have been applied to the solid model to the corresponding finite element model in the following sequence:

1. In ascending volume number order, BFV loads transfer to BFE loads on volume elements, or, if there are none, to BF loads on nodes on volumes (and bounding areas, lines, and keypoints).

2. In ascending area number order, BFA loads transfer to BFE loads on area elements, or, if there are none, to BF loads on nodes on areas (and bounding lines and keypoints).

3. In ascending line number order, BFL loads transfer to BFE loads on line elements, or, if there are none, to BF loads on nodes on lines (and bounding keypoints).

4. BFK loads transfer to BF loads on nodes on keypoints (and on attached lines, areas, and volumes if expansion conditions are met).

Accordingly, for conflicting solid model body loads in "Case C" situations, BFK commands overwrite BFL commands, BFL commands overwrite BFA commands, and BFA commands overwrite BFV commands. For conflicting body loads, a body load specified for a higher line number, area number, or volume number overwrites the body load specified for a lower line number, area number, or volume number, respectively. The body load specification issue order does not matter.

Note-Any conflict detected during solid model body load transfer produces a warning similar to the following:

Changing the value of BFK, BFL, BFA, or BFV constraints between solutions may produce many of these warnings at the 2nd or later solid BC transfer. These can be prevented if you delete the nodal BF loads between solutions using BFVDEL, BFADEL, BFLDEL, and/or BFDELE.

2.6.9 Inertia Loads

The set of commands for inertia loads are listed below:

Table 2-9 Inertia loads commands

Command

GUI Menu Paths

ACEL

Main Menu>Preprocessor>FLOTRAN Set Up>Flow Environment>Gravity
Main Menu>Preprocessor>Loads>Apply>Gravity
Main Menu>Preprocessor>Loads>Delete>Gravity
Main Menu>Solution>FLOTRAN Set Up>Flow Environment>Gravity
Main Menu>Solution>Apply>Gravity
Main Menu>Solution>Delete>Gravity

CGLOC

Main Menu>Preprocessor>FLOTRAN Set Up>Flow Environment>Rotating Coords
Main Menu>Preprocessor>Loads>Apply>Other>Coriolis Effects
Main Menu>Preprocessor>Loads>Delete>Other>Coriolis Effects
Main Menu>Solution>FLOTRAN Set Up>Flow Environment>Rotating Coords
Main Menu>Solution>Apply>Other>Coriolis Effects
Main Menu>Solution>Delete>Other>Coriolis Effects

CGOMGA

Main Menu>Preprocessor>FLOTRAN Set Up>Flow Environment>Rotating Coords
Main Menu>Preprocessor>Loads>Apply>Other>Coriolis Effects
Main Menu>Preprocessor>Loads>Delete>Other>Coriolis Effects
Main Menu>Solution>FLOTRAN Set Up>Flow Environment>Rotating Coords
Main Menu>Solution>Apply>Other>Coriolis Effects
Main Menu>Solution>Delete>Other>Coriolis Effects

DCGOMG

Main Menu>Preprocessor>Loads>Apply>Other>Coriolis Effects
Main Menu>Preprocessor>Loads>Delete>Other>Coriolis Effects
Main Menu>Solution>Apply>Other>Coriolis Effects
Main Menu>Solution>Delete>Other>Coriolis Effects

DOMEGA

Main Menu>Preprocessor>Loads>Apply>Other>Angular Accel
Main Menu>Preprocessor>Loads>Delete>Other>Angular Accel
Main Menu>Solution>Apply>Other>Angular Accel
Main Menu>Solution>Delete>Other>Angular Accel

IRLF

Main Menu>Preprocessor>Loads>Other>Inertia Relief
Main Menu>Preprocessor>Loads>Output Ctrls>Incl Mass Summry
Main Menu>Solution>Other >Inertia Relief
Main Menu>Solution>Output Ctrls>Incl Mass Summry

OMEGA

Main Menu>Preprocessor>Loads>Apply>Other>Angular Velocity
Main Menu>Preprocessor>Loads>Delete>Other>Angular Velocity
Main Menu>Solution>Apply>Other>Angular Velocity
Main Menu>Solution>Delete>Other>Angular Velocity

Notice that there are no specific commands to list or delete inertia loads. To list them, issue STAT, INRTIA (Utility Menu>List>Status>Solution>Inertia Loads) To remove an inertia load, simply set the load value to zero. You can set an inertia load to zero, but you cannot delete it. For ramped load steps, inertia loads are ramped to zero. (This is also true when you apply inertia loads.)

The ACEL, OMEGA, and DOMEGA commands specify acceleration, angular velocity, and angular acceleration, respectively, in global Cartesian directions.

Note-The ACEL command applies an acceleration field (not gravity) to a body. Therefore, to apply gravity to act in the negative Y direction, you should specify a positive Y acceleration.

Use the CGOMGA and DCGOMG commands to specify angular velocity and angular acceleration of a spinning body which is itself revolving about another reference coordinate system. The CGLOC command specifies the location of the reference system with respect to the global Cartesian origin. You can use these commands, for example, to include Coriolis effects in a static analysis.

Inertia loads are effective only if your model has some mass, which is usually supplied by a density specification. (You can also supply mass to the model by using mass elements, such as MASS21, but density is more commonly used and is more convenient.) As with all other data, the ANSYS program requires you to use consistent units for mass. If you are accustomed to the British system of units, you might sometimes wish to use weight density (lb/in3) instead of mass density (lb-sec2/in/in3), for convenience.

Use weight density in place of mass density only under these conditions:

A handy way to specify density so that you can use it readily in either a "convenient," weight-density form or "consistent," mass-density form is to define a parameter for gravitational acceleration, g:

Table 2-10 Ways of specifying density

Convenient Form

Consistent Form

Description

g=1.0

g=386.0

Parameter definition

MP,DENS,1,0.283/g

MP,DENS,1,0.283/g

Density of steel

ACEL,,g

ACEL,,g

Gravity load

2.6.10 Coupled-Field Loads

A coupled-field analysis usually involves applying results data from one analysis as loads in a second analysis. For example, you can apply the nodal temperatures calculated in a thermal analysis as body loads in a structural analysis (for thermal strain). Similarly, you can apply magnetic forces calculated in a magnetic field analysis as nodal forces in a structural analysis. To apply such coupled-field loads, use one of the following:

Command(s):

GUI:

Main Menu>Preprocessor>-Loads->Apply>load type>From source
Main Menu>Solution>Apply>load type>From source

See the ANSYS Coupled-Field Analysis Guide for details about how to use this command in different types of coupled-field analyses.

2.6.11 Axisymmetric Loads and Reactions

For constraints, surface loads, body loads, and Y-direction accelerations, you define loads exactly as they would be for any non-axisymmetric model. However, for concentrated forces the procedure is a little different. For these quantities, input load values of force, moment, etc. are on a "360° basis." That is, the load value is entered in terms of total load around the circumference. For example, if an axisymmetric axial load of 1500 pounds per inch of circumference were applied to a 10-inch diameter pipe (Figure 2-16), the total load of 47,124 lb. (1500*2*5 = 47,124) would be applied to node N as follows:

F,N,FY,47124
Axisymmetric results are interpreted in the same fashion as their corresponding input loads. That is, reaction forces, moments, etc. are reported on a total load (360°) basis.

Axisymmetric harmonic elements require that their loads be supplied in a form that the program can interpret as a Fourier series. The MODE command (Main Menu>Preprocessor>Loads>Other>For Harmonic Ele or Main Menu> Solution>Other>For Harmonic Ele), together with other load commands (D, F, SF, etc.), is required for these elements. See the ANSYS Elements Reference for details.

Figure 2-16 Concentrated axisymmetric loads are defined on a "360° basis"

2.6.11.1 Further Hints and Restrictions

Be careful to specify a sufficient number of constraints to prevent unwanted rigid-body motions, discontinuities, or singularities. For instance, for an axisymmetric model of a solid structure such as a solid bar, a lack of UX constraint along the axis of symmetry can potentially allow spurious "voids" to form in a structural analysis. (See Figure 2-17.)

Figure 2-17 Central constraint for solid axisymmetric structure

2.6.12 Loads to Which the DOF Offers No Resistance

If an applied load acts on a DOF which offers no resistance to it (i.e. perfectly zero stiffness), the ANSYS program ignores the load. For example, consider a series of connected collinear LINK1 elements. Loads normal to the line of the links are ignored when you apply them to interior DOFs. If, however, the links are under tension and stress stiffening is being used, the loads are not ignored because there is resistance (stiffness) in the direction of the loads. The same principle applies to membrane shell elements.

2.7 How to Specify Load Step Options

As mentioned earlier, load step options is a collective name for options that control how loads are used during solution and other options such as output controls, damping specifications, and response spectrum data. Load step options can vary from load step to load step. There are six categories of load step options:

2.7.1 General Options

These include such options as time at the end of a load step in transient and static analyses, number of substeps or the time step size, stepping or ramping of loads, and reference temperature for thermal strain calculations. A brief description of each option follows.

2.7.1.1 The Time Option

The TIME command specifies time at the end of a load step in transient and static analyses. In transient and other rate-dependent analyses, TIME specifies actual, chronological time, and you are required to specify a time value. In other, rate-independent analyses, time acts as a tracking parameter. You can never set time to zero in an ANSYS analysis. If you issue TIME,0 or TIME,<blank>, or if you do not issue the TIME command at all, ANSYS uses the default time value: 1.0 for the first load step, and 1.0 + previous time for other load steps. To start your analysis at "zero" time, such as in a transient analysis, specify a very small value such as TIME,1E-6.

2.7.1.2 Number of Substeps and Time Step Size

For a nonlinear or transient analysis, you need to specify the number of substeps to be taken within a load step. This is done as follows:

Command(s):

GUI:

Main Menu>Preprocessor>Loads>Time/Frequenc>Time & Time Step
Main Menu>Solution>Time/Frequenc>Time & Time Step

Command(s):

GUI:

Main Menu>Preprocessor>Loads>Time/Frequenc>Freq & Substeps
Main Menu>Preprocessor>Loads>Time/Frequenc>Time and Substps
Main Menu>Solution>Time/Frequenc>Freq & Substeps
Main Menu>Solution>Time/Frequenc>Time and Substps

NSUBST specifies the number of substeps, and DELTIM specifies the time step size. By default, the ANSYS program uses one substep per load step.

2.7.1.3 Automatic Time Stepping

The AUTOTS command activates automatic time stepping. Its equivalent GUI paths are:

GUI:

Main Menu>Preprocessor>Loads>Time/Frequenc>Time & Time Step
Main Menu>Solution>Time/Frequenc>Time & Time Step
Main Menu>Preprocessor>Loads>Time/Frequenc>Time and Substps
Main Menu>Solution>Time/Frequenc>Time and Substps

In automatic time stepping, the program calculates an optimum time step at the end of each substep, based on the response of the structure or component to the applied loads. When used in a nonlinear static (or steady-state) analysis, AUTOTS determine the size of load increments between substeps.

2.7.1.4 Stepping or Ramping Loads

When specifying multiple substeps within a load step, you need to indicate whether the loads are to be ramped or stepped. The KBC command is used for this purpose: KBC,0 indicates ramped loads, and KBC,1 indicates stepped loads. The default depends on the discipline and type of analysis. (GUI paths equivalent to KBC are identical to those for the DELTIM and NSUBST commands.)

Some notes about stepped and ramped loads are:

Table 2-11 Handling of ramped loads (KBC=0) under different conditions

Load Type1

Applied in Load Step 1

Introduced in Later Load Steps

DOF Constraints

· Temperatures

· Others

Ramped from TUNIF2

Ramped from zero

Ramped from TUNIF3

Ramped from zero

"Forces"

Ramped from zero

Ramped from zero

Surface Loads

· TBULK

· HCOEF

· Others

Ramped from TUNIF2

Stepped

Ramped from zero

Ramped from TUNIF

Ramped from zero4

Ramped from zero

Body Loads

· Temperatures

· Others

Ramped from TUNIF2

Ramped from BFUNIF3

Ramped from previous TUNIF3

Ramped from previous BFUNIF3

Inertia Loads1

Ramped from zero

Ramped from zero

1. For OMEGA loads, note that the OMEGA itself is linearly ramped; therefore, the resulting force will vary quadratically over the load step.

2. The TUNIF command specifies a uniform temperature at all nodes.

3. In this case, the TUNIF or BFUNIF value from the previous load step is used, not the current value.

4. Temperature-dependent film coefficients are always applied at the value dictated by their temperature function, regardless of the KBC setting.

5. The BFUNIF command is just a generic form of TUNIF, meant to specify a uniform body load at all nodes.

2.7.1.5 Other General Options

You can also specify the following general options:

Command(s):

GUI:

Main Menu>Preprocessor>Loads>Other>Reference Temp
Main Menu>Preprocessor>Loads>Settings>Reference Temp
Main Menu>Solution>Other>Reference Temp
Main Menu>Solution>Settings>Reference Temp

Command(s):

GUI:

Main Menu>Preprocessor>Loads>Other>Reuse Tri Matrix
Main Menu>Solution>Other>Reuse Tri Matrix

Command(s):

GUI:

Main Menu>Preprocessor>Loads>Other>For Harmonic Ele
Main Menu>Solution>Other>For Harmonic Ele

Command(s):

GUI:

Main Menu>Preprocessor>Loads>Magnetics>potential formulation method
Main Menu>Solution>Magnetics>potential formulation method

Command(s):

GUI:

Main Menu>Preprocessor>Loads>ExpansionPass>Range of Solu's
Main Menu>Solution>ExpansionPass>Range of Solu's
Main Menu>Preprocessor>Loads>ExpansionPass>By Load Step
Main Menu>Preprocessor>Loads>ExpansionPass>By Time/Freq
Main Menu>Solution>ExpansionPass>By Load Step
Main Menu>Solution>ExpansionPass>By Time/Freq

2.7.2 Dynamics Options

These are options used mainly in dynamic and other transient analyses. They include the following:

Table 2-12 Dynamic and other transient analyses commands

Command

GUI Menu Paths

Purpose

TIMINT

Main Menu>Preprocessor>Loads>
Time/Frequenc>Time Integration

Main Menu>Solution>Time/Frequenc>
Time Integration

Activates or deactivates time integration effects

HARFRQ

Main Menu>Preprocessor>Loads>
Time/Frequenc>Freq & Substeps

Main Menu>Solution>Time/Frequenc>
Freq & Substeps

Specifies the frequency range of the loads in a harmonic response analysis

ALPHAD

Main Menu>Preprocessor>Loads>
Time/Frequenc>Damping

Main Menu>Solution>Time/Frequenc>Damping

Specifies damping for a structural dynamic analysis

BETAD

Main Menu>Preprocessor>Loads>
Time/Frequenc>Damping

Main Menu>Solution>Time/Frequenc>Damping

Specifies damping for a structural dynamic analysis

DMPRAT

Main Menu>Preprocessor>Loads>
Time/Frequenc>Damping

Main Menu>Solution>Time/Frequenc>Damping

Specifies damping for a structural dynamic analysis

MDAMP

Main Menu>Preprocessor>Loads>
Time/Frequenc>Damping

Main Menu>Solution>Time/Frequenc>Damping

Specifies damping for a structural dynamic analysis

2.7.3 Nonlinear Options

These are options used mainly in nonlinear analyses. They include the following:

Table 2-13 Nonlinear analyses commands

Command

GUI Menu Paths

Purpose

NEQIT

Main Menu>Preprocessor>Loads>Nonlinear> Equilibrium Iter

Main Menu>Solution>Nonlinear>Equilibrium Iter

Specifies the maximum number of equilibrium iterations per substep (default=25)

CNVTOL

Main Menu>Preprocessor>Loads>Nonlinear>
Convergence Crit

Main Menu>Solution>Nonlinear>Convergence Crit

Specifies convergence tolerances

NCNV

Main Menu>Preprocessor>Loads>Nonlinear>
Criteria to Stop

Main Menu>Solution>Nonlinear>Criteria to Stop

Provides options for terminating analyses

2.7.4 Output Controls

Output controls, as their name indicates, control the amount and nature of output from an analysis. There are two primary output controls:

Table 2-14 Output controls commands

Command

GUI Menu Paths

Purpose

OUTRES

Main Menu>Preprocessor>Loads>
Output Ctrls>DB/Results File

Main Menu>Solution>Output Ctrls>DB/Results File

Controls what ANSYS writes to the database and results file and how often it is written.

OUTPR

Main Menu>Preprocessor>Loads>
Output Ctrls>Solu Printout

Main Menu>Solution>Output Ctrls>Solu Printout

Controls what is printed (written to the solution output file, Jobname.OUT) and how often it is written.

The example below illustrates using OUTRES and OUTPR:

OUTRES,ALL,5	! Writes all data every 5th substep
OUTPR,NSOL,LAST	! Prints nodal solution for last substep only
You can issue a series of OUTPR and OUTRES commands (up to 50 of them combined) to meticulously control the solution output, but be aware that the order in which they are issued is important. For example, the commands shown below will write all data to the database and results file every 10th substep and nodal solution data every fifth substep.

OUTRES,ALL,10
OUTRES,NSOL,5
However, if you reverse the order of the commands (as shown below), the second command essentially overrides the first, resulting in all data being written every 10th substep and nothing every 5th substep.

OUTRES,NSOL,5
OUTRES,ALL,10
Note-The program default for writing out solution data for all elements depends on analysis type; see the description of OUTRES in the ANSYS Commands Reference. To restrict the solution data that is written out, use OUTRES to selectively suppress (FREQ = NONE) the writing of solution data, or first suppress the writing of all solution data (OUTRES,ALL,NONE) and then selectively turn on the writing of solution data with subsequent OUTRES commands.

A third output control command, ERESX, allows you to review element integration point values in the postprocessor.

Command(s):

GUI:

Main Menu>Preprocessor>Loads>Output Ctrls>Integration Pt
Main Menu>Solution>Output Ctrls>Integration Pt

By default, the ANSYS program extrapolates nodal results that you review in the postprocessor from integration point values for all elements except those with active material nonlinearities (for instance, non-zero plastic strains). By issuing ERESX,NO, you can turn off the extrapolation and instead copy integration point values to the nodes, making those values available in the postprocessor. Another option, ERESX,YES, forces extrapolation for all elements, whether or not they have active material nonlinearities.

2.7.5 Biot-Savart Options

These are options used in a magnetic field analysis. The two commands in this category are as follows:

Table 2-15 Biot-Savart commands

Command

GUI Menu Paths

Purpose

BIOT

Main Menu>Preprocessor>Loads>Magnetics>
Biot-Savart

Main Menu>Solution>Magnetics>Biot-Savart

Calculates the magnetic source field intensity due to a selected set of current sources.

EMSYM

Main Menu>Preprocessor>Loads>Magnetics>
Copy Sources

Main Menu>Solution>Magnetics>Copy Sources

Duplicates current sources that exhibit circular symmetry.

The ANSYS Electromagnetic Field Analysis Guide explains the use of these commands where appropriate.

2.7.6 Spectrum Options

There are many commands in this category, all meant to specify response spectrum data and power spectral density (PSD) data. You use these commands in spectrum analyses, as described in the ANSYS Structural Analysis Guide.

2.8 Creating Multiple Load Step Files

All loads and load step options put together form a load step, for which the program can calculate the solution. If you have multiple load steps, you can store the data for each load step on a file, called the load step file, and read it in later for solution.

The LSWRITE command writes the load step file (one file per load step, identified as Jobname.S01, Jobname.S02, Jobname.S03, etc.). Use one of these methods:

Command(s):

GUI:

Main Menu>Preprocessor>Loads>Write LS File
Main Menu>Solution>Write LS File

After all load step files are written, you can use one action command to read in the files sequentially and obtain the solution for each load step (see Chapter 3).

The sample set of commands shown below defines multiple load steps:

/SOLU               	! Enter SOLUTION
...
!  Load Step 1:
D,...       	! Loads
SF,...
...
NSUBST,...        	! Load step options
KBC,...
OUTRES,...
OUTPR,...
...
LSWRITE         	! Writes load step file: Jobname.S01
!  Load Step 2:
D,...        	! Loads
SF,...
...
NSUBST,...        	! Load step options
KBC,...
OUTRES,...
OUTPR,...
...
LSWRITE          	! Writes load step file: Jobname.S02
...
See the ANSYS Commands Reference for descriptions of the NSUBST, KBC, OUTRES, OUTPR and LSWRITE commands.

Some notes about the load step file:

GUI:

Main Menu>Preprocessor>Loads>Read LS File
Main Menu>Solution>Read LS File

GUI:

Main Menu>Preprocessor>Loads>Operate>Delete LS Files
Main Menu>Solution>Operate>Delete LS Files

GUI:

Main Menu>Preprocessor>Loads>Delete>All Load Data>data type
Main Menu>Preprocessor>Loads>Reset Options
Main Menu>Preprocessor>Loads>Settings>Reset Factors
Main Menu>Solution>Reset Options
Main Menu>Solution>Settings>Reset Factors


Go to the beginning of this chapter